ABB NDBU-95 is an AC system power module for the Bailey Infi 90 and Net 90 AC Modular Power System, taking 120/240 VAC at the module mounting unit backplane and converting it first to a 325 VDC nominal primary voltage and then to regulated +5, +15, –15 and +24 VDC outputs. The regulated voltages leave the module through the system power bus bar to supply other module mounting units and process control modules in the cabinet, and the module can be inserted or removed from its mounting unit while the system is under power.
Product Datasheet
- Brand: ABB
- Model:NDBU-95
- System: Bailey Infi 90 / Net 90 AC Modular Power System
- AC Input: 120/240 VAC at the module mounting unit backplane
- Primary Voltage: 325 VDC nominal
- Regulated Outputs: +5 VDC, +15 VDC, –15 VDC, +24 VDC
- Power Distribution: System power bus bar to module mounting units and process control modules
- Service Access: Module can be inserted or removed while the mounting unit is under power
Fault Troubleshooting and Common Questions
- The cabinet has no DC output or reports a power fault. Check the AC feed at the power entry panel, the circuit breaker and the fan assembly, and verify the module is fully seated in its mounting unit. Confirm the status output to the alarm circuit and check the power bus bar connections to the other mounting units.
- One of the regulated outputs is low, high or missing. Measure +5, +15, –15 and +24 VDC at the bus bar and compare against the module’s regulation. Check for an overloaded or shorted load on that rail, and verify the primary 325 VDC is present at the module.
- The module runs hot or the cabinet overheats. Check the fan assembly and airflow through the cabinet, verify the ambient temperature is within the cabinet’s rating, and confirm the installed module capacity covers the connected load. Inspect the module’s heat sink and vents for blockage.
Safety Precautions
- Isolate the AC feed and follow lockout/tagout procedures before servicing the power entry panel or module.
- Treat the primary 325 VDC section as hazardous; discharge and verify before touching internal circuits.
- Verify bus bar, mounting unit and alarm wiring before energizing the cabinet.
- Do not exceed the cabinet’s rated load or remove modules that the power budget requires.
- Use qualified personnel for installation, maintenance and troubleshooting of the power system.

Company Overview
Main Products
We specialize in supplying original imported spare parts for DCS, PLC, robotics, and large servo systems from leading global brands, including:
- FOXBORO | EMERSON | TRICONEX | XYCOM | BENTLY
- ROCKWELL | ABB | GE | Aen-Brady | YOKOGAWA
- HONEYWELL | RELIANCE | SCHNEIDER | MODICO
- Westinghouse | WOODWARD | Motorola | Rexroth | SEW
☀️Tiana Lai(Sales Director)
?Email: ydf8801@163.com
?️Ship to you via DHL/TNT/UPS/EMS/Fedex
?Product Condition: One-year warranty
Contact us immediately to embark on a new experience of efficient procurement! ✨












There are no reviews yet.