ABB SYN5202A-Z V277 SYNCHROTACT 5 Synchronizer
ABB SYN5202A-Z V277 is an automatic dual-channel synchronizing device of the SYNCHROTACT 5 generation, built as two independently structured channels in one casing: channel 1 performs automatic synchronization with voltage and frequency adjustment, while channel 2 acts as an independent synchrocheck monitoring channel connected in series. It is used to parallel generators with power lines, to parallel synchronous or asynchronous lines and busbars, and to monitor manual paralleling, with up to seven parameter sets for seven different paralleling points.
Key Features
- Automatic dual-channel synchronizing device in one casing
- Channel 1: automatic synchronization with voltage and frequency matching
- Channel 2: independent synchrocheck monitoring in series with channel 1
- Two channels with different hardware and software structures for maximum safety
- Automatic synchronization of generators with power lines
- Paralleling of synchronous and asynchronous lines, transmission lines and busbars
- Synchrocheck function for manual paralleling
- Dead bus / dead line feature
- Up to seven parameter sets for seven paralleling points
- One device can synchronize up to seven power circuit breakers
- Operating frequencies 50 Hz, 60 Hz and 16 2/3 Hz
- Freely configurable digital inputs and outputs, all isolated
- Remote control via Modbus, Profibus or LON fieldbus
- Remote servicing via TCP/IP and Ethernet
- Commissioning and maintenance with the SynView PC tool on Windows
- No separate power supply unit required
Technical Specifications
- Type Designation: SYN 5202 (variant SYN5202A-Z, V277)
- Product Type: Automatic dual-channel synchronizing device
- Channels: 2 (automatic synchronization + synchrocheck)
- Auxiliary Voltage, Nominal: 24–250 VDC; 100–230 VAC
- Auxiliary Voltage, Permissible: 18–300 VDC; 75–300 VAC
- Maximum Power Consumption: 25 W / 35 VA (READY and OPERATING)
- Measuring Inputs U1, U2: 50–130 VAC nominal
- Voltage Range: 0 to 130% Un
- Nominal Frequency: 16 2/3 Hz, 50 Hz, 60 Hz
- Frequency Range: 10–100 Hz
- Digital Inputs: 24/48 VDC, 6–8 mA
- Paralleling Relay Contacts: 250 VAC/VDC maximum, 10 A continuous, 1500 VA/W switching ON, 1500/150 VA/W switching OFF (resistive)
- Command and Signaling Relay Contacts: 250 VAC/VDC maximum, 1.5 A continuous, 50 VA/W
- Slip Limit Setting Range: 0–6% (channel 1), step 0.01%
- Angle Limit Setting Range: 1–99° (channel 1), step 1°
- Maximum Voltage Difference: 0–40%, step 1%
- Paralleling Time: 0–990 ms, step 10 ms
- Paralleling Command Duration: 50–990 ms, step 10 ms
- Dead Bus Zero Voltage: 0–49%, step 1%
- Voltage Matcher: 0–5%/s adjustment characteristic, 1–20 s pulse interval
- Frequency Matcher: 0–5%/s adjustment characteristic, 1–120 s pulse interval
- PC Interface: Ethernet (SynView), bridgeable distance 100 m
- Dielectric Test: 2 kV (IEC 60255-5)
- Impulse Voltage Test: 5 kV (IEC 60255-5)
- Operating Temperature (with communication): +5 °C to +55 °C
- Functionable Temperature: +5 °C to +70 °C
- Storage Temperature: -10 °C to +85 °C
- Protection Degree: IP 54 front, IP 50 rear
- Weight: 4 kg
- Standards: IEC 60255-6, EN 50263, CE (EMC 2014/30/EU, LVD 2014/35/EU)
Installation Notes
- Verify the auxiliary voltage before connection: 24–250 VDC or 100–230 VAC nominal, within 18–300 VDC or 75–300 VAC.
- Connect the line/bus voltage U1 and generator voltage U2 to the measuring inputs, observing the 50–130 VAC nominal range and correct phase identification.
- Wire the paralleling relay to the circuit breaker close circuit, respecting the 10 A continuous and 1500 VA/W switching limits.
- Connect the voltage regulator (U+, U-) and governor (f+, f-) adjusting commands to the corresponding command relays.
- Set the slip, angle and voltage-difference limits for channel 1, and match channel 2 settings to channel 1.
- Commission the device with SynView, verify the READY, OPERATING and ERROR indications, and test the synchrocheck release before enabling automatic paralleling.
![]()
Company Overview
Main Products
We specialize in supplying original imported spare parts for DCS, PLC, robotics, and large servo systems from leading global brands, including:
- FOXBORO | EMERSON | TRICONEX | XYCOM | BENTLY
- ROCKWELL | ABB | GE | Aen-Brady | YOKOGAWA
- HONEYWELL | RELIANCE | SCHNEIDER | MODICO
- Westinghouse | WOODWARD | Motorola | Rexroth | SEW
☀️Tiana Lai(Sales Director)
?Email: ydf8801@163.com
?️Ship to you via DHL/TNT/UPS/EMS/Fedex
?Product Condition: One-year warranty
Contact us immediately to embark on a new experience of efficient procurement! ✨












There are no reviews yet.