Call us 24/7+86 18250705533

EATON APR24 Access Power Rectifier 24 V

In stock

Eaton APR24 is a 24 V DC access power rectifier built as a 3U Eurocard module, delivering 750 W and 31 A at 24 V from a 240 V AC single-phase supply. It holds full output from 185 to 275 V rms and keeps running down to 150 V rms at 30 °C, with an adjustable 21.5–29 V output preset at 27 V for 24 V battery strings. Current limit, over-temperature turndown, over-voltage shutdown within 3 ms and full short-circuit recovery are all built in, and green, amber and red LEDs report status at the front. Fitted into a rectifier shelf with a supervisory module, it powers telecom access sites, base stations and SCADA stations on 24 V DC plants.


•Manager: Tiana Lai

•E-mail: ydf8801@163.com

•Ship to you via Fedex/DHL/TNT/UPS/EMS

•Package: Original packing with cartons

SKU: 6125637-1-1-1-2-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1
wechatPhone +8618250705533
Phone: +86 18250705533
Email: sales5@xrjdcs.com
connect:Jinny
Image 2

Product Overview

The Eaton APR24 is a 24 V DC access power rectifier built as a 3U Eurocard plug-in module. It converts a 240 V AC single-phase supply into a regulated 24 V DC output of up to 750 W (31 A), and it is designed to sit in a rectifier shelf alongside a supervisory module that handles battery charging and load sharing. The front carries three status LEDs, cooling is by a temperature-controlled fan, and the DC output is adjustable across the 21.5–29 V window needed for 24 V battery strings.

Key Specifications

  • Manufacturer: Eaton
  • Model: APR24
  • Product Type: Access power rectifier, 24 V DC
  • Nominal AC Input: 240 V
  • Rated AC Operating Range: 185–275 V rms, full output up to 50 °C
  • Extended AC Range: 150–185 V rms, full output up to 30 °C; 90–300 V rms with reduced output below 150 V
  • Frequency Range: 45–66 Hz
  • Maximum Input Current: 6 A rms (150 V AC, 20 °C)
  • Efficiency: 88 % typical (50–100 % load, 230 V AC)
  • Power Factor: >0.99 (50–100 % load)
  • THD: <5 % (50–100 % load, rated AC voltage)
  • Nominal DC Output: 24 V
  • Adjustable Output Range: 21.5–29 V
  • Rated Output Power: 750 W
  • Rated Output Current: 31 A at 24 V
  • Preset Output Voltage: 27 V ± 0.1 V (manufacturer preset)
  • Regulation: ±0.1 V
  • Hold-up Time: 7 ms
  • Ripple: <10 mV rms (<100 Hz)
  • Noise, Wideband: <10 mV rms (5 Hz–1 MHz)
  • Noise, Peak-to-Peak: <200 mV p-p (0–20 kHz)
  • Current Limit: Factory set to 31 A
  • Over-Voltage Shutdown: <3 ms delay
  • Short-Circuit Protection: Output limited to <130 % of rated current, self-recovering
  • Polarity Reversal: Crowbar diode and fuse in the negative output
  • Operating Temperature: -10 °C to +50 °C rated; -40 °C to +70 °C extended with derating
  • Humidity: <95 % RH, non-condensing
  • Altitude: <2000 m
  • Dimensions (H × W × D): 3U (133 mm) × 13E (66 mm) × 257 mm
  • Weight: 1.9 kg
  • Connector: H16 Eurocard male
  • Cooling: Temperature-controlled high-reliability fan
  • Front LEDs: Green (power on), amber (non-urgent alarm), red (urgent alarm)

Key Features

  • 750 W in a 3U Card: A full 31 A at 24 V from a single Eurocard module, so a shelf builds capacity by adding rectifiers rather than sizing one large unit.
  • Wide AC Window: Holds full output from 185 to 275 V rms, and keeps running down to 150 V rms at 30 °C — useful where the AC supply is weak or heavily loaded.
  • Battery-Ready Output Range: 21.5–29 V adjustment covers 24 V lead-acid strings, with the output preset at 27 V from the factory.
  • Supervisory Module Control: Constant-voltage operation with automatic voltage control enabled from the rack supervisory module, and a fail-safe fallback to the preset voltage if system communication is lost.
  • Layered Protection: Current limit, over-temperature turndown, over-voltage shutdown within 3 ms, crowbar and fuse on the negative output, and full short-circuit protection that recovers automatically.
  • Front Status Indication: Green, amber and red LEDs report power on, current-limit (non-urgent) alarm and urgent alarm directly at the module face.
  • Eurocard Connector: H16 male connector plugs into the shelf backplane for input, output and alarms.

Typical Applications

  • Telecom access networks and remote sites running 24 V DC plants
  • Cellular base stations and radio trunk installations
  • SCADA and telemetry stations with 24 V battery backup
  • Light industrial DC power systems built on 3U rectifier shelves
  • Capacity expansion or replacement of a failed rectifier in an existing shelf

EATON APR24 Access Power Rectifier 24 V EATON APR24 Access Power Rectifier 24 V EATON APR24 Access Power Rectifier 24 V




    Customers reviews

    There are no reviews yet.

    Be the first to review “EATON APR24 Access Power Rectifier 24 V”

    لن يتم نشر عنوان بريدك الإلكتروني. الحقول الإلزامية مشار إليها بـ *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +86 18250705533
    to whats
    +8618250705533
    to whats
    +8618250705533
    email: sales5@xrjdcs.com