EATON FAZ-C2-2-DC 2 Pole C Curve DC Miniature Circuit Breaker 2A
🔨Key Specifications
- Brand: Eaton
- Model / Part No: FAZ-C2/2-DC
- Catalog Number: 279134
- EAN: 4015082791346
- Product Type: Miniature circuit breaker (MCB), thermal-magnetic
- Poles: 2-pole (both poles protected)
- Rated Current (In): 2 A
- Trip Characteristic: Type C (medium inrush)
- Voltage Type: DC
- Rated Operational Voltage: 250 V DC per pole (max system voltage depends on series connection; 2-pole common use up to 500 V DC nominal in series context, confirm per drawing)
- Insulation Voltage (Ui): 440 V
- Impulse Withstand (Uimp): 4 kV
- Breaking Capacity (Icu): 10 kA per IEC/EN 60947-2
- Standards: IEC/EN 60947-2, IEC/EN 60898, UL 1077, CSA C22.2 No. 235, CE
- Certifications: UL Recognized, CSA Certified, EN 45545-2 (railway), IEC 61373 (shock/vibration)
- Mounting: 35 mm DIN rail (IEC/EN 60715), 17.5 mm per pole (2 modules wide)
- Terminals: Screw, twin-purpose; 1–25 mm² solid/stranded
- Protection: IP20 (IP40 when enclosed)
- Operating Temp: -25 °C to +75 °C
- Electrical Life: ≥ 10,000 operations
- Back-up Fuse: max 100 A gL/gG
🔨Key Features
- DC-Optimized Arc Interruption: Dual-break contacts + arc chutes for safe DC fault clearing.
- Type C Curve: Tolerates moderate inrush; trips on real overload/short-circuit.
- High Breaking Capacity: 10 kA at DC application per IEC 60947-2.
- Clear Status Indication: Front toggle shows ON/OFF/tripped position (red/green).
- Trip-Free Mechanism: Cannot be held closed during fault.
- Finger-Safe Terminals: Touch-safe design per EN 50274.
- Accessory-Ready: Supports aux contacts, shunt trips (FAZ-X accessories).
- Compact DIN Form: 17.5 mm/pole, saves panel space.
🔨Typical Applications
- DC control circuits for PLC, sensors, relays, instrumentation
- Photovoltaic (PV) string and combiner-box protection
- UPS output and battery bank branch protection
- DC power supplies, converters, excitation auxiliaries
- Railway and mobile equipment panels (EN 45545-2 / IEC 61373)
- Industrial automation and building DC distribution
🔷Ordering & Installation Notes
- Exact match: FAZ-C2/2-DC = 2 A, 2-pole, C-curve, DC-rated. Do not substitute AC-only FAZ-C2/2.
- Polarity matters: DC supply direction is polarity-dependent — follow Eaton wiring diagram.
- Voltage stacking: 2-pole series extends DC rating; verify per-pole 250 V DC vs total string voltage.
- Upstream protection: Use coordinated gL/gG fuse (≤100 A) if required by design.
- Torque & seating: DIN rail click-mount; torque screw terminals to Eaton spec; clean busbar edges.













There are no reviews yet.