GE IC200ALG327H is a 24 V DC source Genius I/O block with 16 circuits that can each be configured as input, tristate input or output, rated 2 A per circuit with short circuit, overload, no-load and overtemperature diagnostics for discrete sensing and actuation on a Genius serial bus.


•Manager: Tiana Lai

•E-mail: ydf8801@163.com

•Ship to you via Fedex/DHL/TNT/UPS/EMS

•Package: Original packing with cartons

SKU: 6125637-1-1-1-2-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1
wechatPhone +8618250705533
Phone: +86 18250705533
Email: sales5@xrjdcs.com
connect:Jinny
Image 2

GE IC200ALG327H VersaMax 12 Channel Analog Output

GE IC200ALG327H is a 24 V DC source-type Genius I/O block with 16 discrete circuits, each independently configurable as an input, tristate input or output. Outputs source current to field devices, inputs accept 2-wire and 3-wire solid state or electromechanical sensors, and control power is taken from the device voltage wired to the terminals, so no separate block power supply is required. The block communicates on the Genius serial bus and provides per-circuit electronic diagnostics including short circuit, overload, no-load, failed switch and overtemperature detection.

Product Datasheet

  • Brand: GE
  • Model: IC200ALG327H
  • Product Name: 24 V DC Source 16-Circuit Source I/O Block
  • Circuits: 16 discrete circuits, each configurable as input, tristate input or output
  • Block Type: Source (outputs source current; inputs referenced to DC+)
  • Operating Voltage: 18 to 30 V DC
  • Sensor Compatibility: 2-wire and 3-wire solid state sensors and electromechanical sensors
  • Output Current: 2 A per circuit steady state
  • Maximum Inrush Current: 10 A for up to 10 ms
  • Block Output Current: 15 A at 35 °C
  • Output OFF Leakage: 1.0 mA
  • Output Turn-On Delay: 1 ms maximum
  • Output Voltage Drop: 2.0 V maximum at 2 A inrush
  • Minimum Recommended Load: 50 mA with no-load detection disabled
  • Maximum Switching Frequency: Once per second with high inrush current
  • Input ON Level: 16 to 24 V DC (24 V supply)
  • Input OFF Level: 0 to 7 V DC
  • Input Processing Time: 1.7 ms typical, plus selectable filter delay
  • Selectable Input Filter: 5 to 100 ms
  • Required DC Power: 150 mA typical, 300 mA maximum
  • Power Supply Dropout Time: 10 ms
  • Maximum Ripple: 10%
  • Block-to-Block Isolation: 1,500 V
  • Diagnostics: Short circuit, overload, no load, failed switch, overtemperature; open wire detection for tristate inputs
  • Indicators: Unit OK and I/O Enabled LEDs, plus an individual load-side indicator per circuit
  • Dimensions: 22.44 cm height x 9.05 cm width x 11.23 cm depth
  • Weight: 1.8 kg (4 lb)
  • Heat Dissipation: 68.8 W with 16 outputs on at 2 A
  • Operating Temperature: 0 to 60 °C
  • Humidity: 5% to 95%, non-condensing
  • Vibration: 5 to 10 Hz at 0.2 inch displacement, 10 to 200 Hz at 1 G

Safety Precautions

  • Isolate power and follow lockout/tagout procedures before wiring or removing the block.
  • Use electrostatic discharge protection when handling the electronics assembly.
  • Connect the green ground screw to a reliable ground; mounting screws alone do not ground the block.
  • Do not connect field devices until the operating voltage and circuit ratings have been confirmed.
  • Use qualified personnel for installation, configuration and troubleshooting on operating Genius bus systems.

GE IC200ALG327H VersaMax 12 Channel Analog Output GE IC200ALG327H VersaMax 12 Channel Analog Output GE IC200ALG327H VersaMax 12 Channel Analog Output




    Customers reviews

    There are no reviews yet.

    Be the first to review “GE IC200ALG327H VersaMax 12 Channel Analog Output”

    لن يتم نشر عنوان بريدك الإلكتروني. الحقول الإلزامية مشار إليها بـ *

    Search for products

    Back to Top
    Product has been added to your cart
    phone: +86 18250705533
    to whats
    +8618250705533
    to whats
    +8618250705533
    email: sales5@xrjdcs.com