GE IC200ALG327H VersaMax 12 Channel Analog Output
GE IC200ALG327H is a 24 V DC source-type Genius I/O block with 16 discrete circuits, each independently configurable as an input, tristate input or output. Outputs source current to field devices, inputs accept 2-wire and 3-wire solid state or electromechanical sensors, and control power is taken from the device voltage wired to the terminals, so no separate block power supply is required. The block communicates on the Genius serial bus and provides per-circuit electronic diagnostics including short circuit, overload, no-load, failed switch and overtemperature detection.
Product Datasheet
- Brand: GE
- Model: IC200ALG327H
- Product Name: 24 V DC Source 16-Circuit Source I/O Block
- Circuits: 16 discrete circuits, each configurable as input, tristate input or output
- Block Type: Source (outputs source current; inputs referenced to DC+)
- Operating Voltage: 18 to 30 V DC
- Sensor Compatibility: 2-wire and 3-wire solid state sensors and electromechanical sensors
- Output Current: 2 A per circuit steady state
- Maximum Inrush Current: 10 A for up to 10 ms
- Block Output Current: 15 A at 35 °C
- Output OFF Leakage: 1.0 mA
- Output Turn-On Delay: 1 ms maximum
- Output Voltage Drop: 2.0 V maximum at 2 A inrush
- Minimum Recommended Load: 50 mA with no-load detection disabled
- Maximum Switching Frequency: Once per second with high inrush current
- Input ON Level: 16 to 24 V DC (24 V supply)
- Input OFF Level: 0 to 7 V DC
- Input Processing Time: 1.7 ms typical, plus selectable filter delay
- Selectable Input Filter: 5 to 100 ms
- Required DC Power: 150 mA typical, 300 mA maximum
- Power Supply Dropout Time: 10 ms
- Maximum Ripple: 10%
- Block-to-Block Isolation: 1,500 V
- Diagnostics: Short circuit, overload, no load, failed switch, overtemperature; open wire detection for tristate inputs
- Indicators: Unit OK and I/O Enabled LEDs, plus an individual load-side indicator per circuit
- Dimensions: 22.44 cm height x 9.05 cm width x 11.23 cm depth
- Weight: 1.8 kg (4 lb)
- Heat Dissipation: 68.8 W with 16 outputs on at 2 A
- Operating Temperature: 0 to 60 °C
- Humidity: 5% to 95%, non-condensing
- Vibration: 5 to 10 Hz at 0.2 inch displacement, 10 to 200 Hz at 1 G
Safety Precautions
- Isolate power and follow lockout/tagout procedures before wiring or removing the block.
- Use electrostatic discharge protection when handling the electronics assembly.
- Connect the green ground screw to a reliable ground; mounting screws alone do not ground the block.
- Do not connect field devices until the operating voltage and circuit ratings have been confirmed.
- Use qualified personnel for installation, configuration and troubleshooting on operating Genius bus systems.













There are no reviews yet.