1️⃣Product Overview
The ICS Triplex T8461 is a 40-channel Triple Modular Redundant (TMR) digital output module for the Trusted safety instrumented system (SIS). Each channel is fully triplicated and voted 2-out-of-3, with 24 V DC / 48 V DC output capability at 0.75 A per channel, organized into 5 isolated banks of 8 channels. With per-channel line monitoring, automatic overcurrent protection, and 1 ms SOE reporting, it is a SIL 3-rated output module for emergency shutdown, fire and gas, and critical interlock applications.
2️⃣Key Specifications
- Manufacturer: ICS Triplex
- Model / Part Number: T8461
- Product Series: Trusted TMR (Triple Modular Redundant) SIS
- Product Type: Digital Output Module (TMR)
- Number of Channels: 40
- Output Voltage: 24 V DC / 48 V DC (field output 18–58 V DC)
- Output Current: 0.75 A per channel; 6 A per power group
- Channel Grouping: 5 isolated banks of 8 channels
- Backplane Supply: 20–32 V DC (24 V DC nominal)
- Module Power: 27 W
- Isolation: 2500 V impulse withstand opto/galvanic barrier
- Line Monitoring: Automatic per-channel open/short circuit and load fault detection
- Protection: Automatic overcurrent protection per channel (no external fuses required)
- SOE: Onboard sequence-of-events reporting, 1 ms resolution
- Safety Rating: SIL 3 (IEC 61508)
- Approvals: Ordinary location / Hazardous Location / ATEX / IECEx
3️⃣Key Features
- 40 TMR Output Channels: Triple-redundant channels with 2oo3 voting for fail-safe outputs.
- 24 V / 48 V DC Flexibility: Drives solenoids, relays, and interlock devices at either field voltage.
- Automatic Line Monitoring: Detects open circuit, short circuit, and load faults per channel.
- No External Fuses: Automatic overcurrent protection per channel simplifies panel design.
- 2500 V Isolation Barrier: Opto/galvanic isolation protects the system from field transients.
- Onboard SOE: 1 ms resolution event recording supports sequence-of-events analysis.
4️⃣Typical Applications
- Emergency shutdown (ESD) and safety interlock outputs in SIL 3 loops
- Fire and gas system final-element driving
- Burner management and critical trip outputs
- Spare-part supply for installed Trusted TMR systems
5️⃣Ordering Notes
- Revision variants: T8461 vs T8461C (current revision) and T8461CX (non-RoHS) — confirm the exact suffix against the installed module.
- Field termination: Pairs with the corresponding Trusted field termination assembly; verify the FTA model and cable for your cabinet.
- Voltage check: Confirm the field output voltage (24 V DC vs 48 V DC) required by your loads.